TRIP LED solid Red

Solid Red TRIP LED — Compressor not running despite thermostat demand

Bryant · Comfort Alert Diagnostic Module

¿Qué significa TRIP LED solid Red ?

The thermostat is calling for cooling (Y signal is present), but the compressor is not running. This indicates a protection mechanism has engaged or there's a power issue to the compressor.

Causas comunes

  • Compressor protector has opened.
  • Condensing unit power disconnect is open.
  • Compressor circuit breaker or fuse is open.
  • Broken supply wires or connector.
  • Compressor power wires not routed through the Comfort Alert module.
  • Compressor contactor has failed open.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Turn off unit power supply and install a lockout tag.

  2. 2

    Check if the thermostat demand signal (Y) is present.

  3. 3

    Verify the compressor protector is closed.

  4. 4

    Inspect the condensing unit power disconnect and circuit breaker/fuses.

  5. 5

    Check for continuity in supply wires and connectors.

  6. 6

    Ensure compressor contactor is functioning correctly.

Ver todos los códigos en este manual (55)
Datos técnicos verificados. Última actualización: April 2026

Fallas relacionadas

ALERT LED * flashes Yellow (misreported)Yellow ALERT LED * flashes (misreported) — Welded Contactor checkALERT LED 2 flashes YellowYellow ALERT LED 2 flashes — System pressure trip or compressor overloadALERT LED 3 flashes YellowYellow ALERT LED 3 flashes — Compressor short cycling
Fuente: Bryant Comfort Alert Diagnostic Module