5514

Warning Z1 Evap. Pressure on JR0 too low — Low evaporator pressure detected

Bosch · Alarm List A/W Split (8754) 2018 01 10

¿Qué significa 5514 ?

This warning is issued if the temperature of JR0 drops below the allowed range (below -27°C) for more than 30 seconds. It suggests a blockage or low airflow in the air heat exchanger.

Causas comunes

  • Blocked or low airflow through the air heat exchanger of the heat pump.
  • 230 V supply voltage is missing from the fan.
  • 0-10 V control signal is missing for the fan.
  • One of the expansion valves is stuck closed.
  • Defective I/O module.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Ensure sufficient airflow through the air heat exchanger.

  2. 2

    Check if 230V voltage is available on output PL3, terminal 32 (78, N).

  3. 3

    Check the 0-10V voltage on output PL3 PWM, terminal 20 (20, 26) using the test function for the outdoor unit.

  4. 4

    Check control cables to the expansion valves and run a test cycle to verify they open.

  5. 5

    If voltages are missing, replace the I/O module. If voltages are present but the fan doesn't run, replace the fan.

Ver todos los códigos en este manual (60)