Bosch · Alarm List A/W Split (8754) 2018 01 10
The electrical heater's overheating protector or the heating system's pressure guard (MC1) has been triggered. This can be due to low pressure (<0.5 bar) or overheating.
Haga clic en los pasos para seguir su progreso.
De-air the heating system and refill if necessary.
Clean the filter ball SC1 on the return pipe.
Check heating system adjustment valves and thermostats.
Replace fuse F1 or F50 if blown.
Verify the breaking temperature of the overheating protector (96°C).
Ensure 230V supply to the circulation pump PC0 and check the PWM signal.