Mitsubishi Electric · Air Conditioning
A resistance reading of 1 Megaohm or higher for the indoor fan motor indicates an open circuit, meaning the motor is not functioning electrically.
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
Turn off the power supply to the unit.
Disconnect the indoor fan motor connector (CN211).
Measure the resistance between the specified terminals of the indoor fan motor connector.
If the resistance is 1MΩ or more, replace the indoor fan motor.
Also, replace the fuse (F11) as it may have blown due to the motor issue.