A0-A8

Outdoor Board LED1 (green) blinks three times and LED2 (red) blinks one time alternately - Serial communication error (between outdoor controller board and outdoor power board)

MHI · Air Conditioning

Was bedeutet A0-A8 ?

During startup or operation, the outdoor unit's LED1 (green) blinks three times and LED2 (red) blinks one time alternately, indicating a serial communication error between the outdoor controller board and the outdoor power board.

Häufige Ursachen

  • Connector (CN4) on outdoor controller board and outdoor power board is disconnected or poorly connected.
  • Poor connection of connectors on outdoor controller board (CNMNT and CNVMNT).

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check if connector (CN4) on the outdoor controller board and outdoor power board is not disconnected.

  2. 2

    Check if there is poor connection of connectors on the outdoor controller board (CNMNT and CNVMNT).

  3. 3

    Re-check the error by turning off the main power, waiting, and turning it back on.

Alle Codes in diesem Handbuch durchsuchen (124)
Verifizierte technische Daten. Zuletzt aktualisiert: April 2026

Verwandte Fehlercodes

00Outdoor Board LED only green lights up after startup - No outdoor unit of address 0 / Remote controller transmission wire open1OPERATION INDICATOR lamp blinks 1 time (Pattern A) - Indoor/outdoor unit communication error (Transmitting error - Outdoor unit)14OPERATION INDICATOR lamp blinks 14 times (Pattern A) - Other errors