Co-b4

Co-b4 — Communication loss with compressor B4 board

Carrier · Pro-Dialog Control

What does Co-b4 mean?

Communication has been lost with the control board for compressor B4. This could be due to a bus fault or a defective slave board. The compressor is shut down.

Common Causes

  • Installation bus fault.
  • Defective slave board for compressor B4.
  • Loose wiring connection to the slave board.
  • Interference on the communication bus.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check all wiring connections to the compressor B4 slave board.

  2. 2

    Inspect the communication bus for damage or interference.

  3. 3

    Attempt to reset the communication by cycling power to the unit.

  4. 4

    If the issue persists, the slave board may need replacement.