Carrier Air Conditioning

60 fault codes documented

A051

A051 - Compressor 1 Stuck On Failure

This alarm indicates that Compressor 1 in Circuit A is stuck in the 'on' position. The system will turn off all compressors to prevent damage.

A052

A052 - Compressor 2 Stuck On Failure

This alarm indicates that Compressor 2 in Circuit A is stuck in the 'on' position. The system will turn off all compressors.

A055

A055 - Compressor 1 Stuck On Failure (Circuit B)

This alarm indicates that Compressor 1 in Circuit B is stuck in the 'on' position. The system will turn off all compressors.

A056

A056 - Compressor 2 Stuck On Failure (Circuit B)

This alarm indicates that Compressor 2 in Circuit B is stuck in the 'on' position. The system will turn off all compressors.

A120

A120 - Circuit A Low Saturated Suction Temperature Alarm

An alarm for low suction temperature in Circuit A has been triggered. The circuit will stop to protect the compressor.

A121

A121 - Circuit B Low Saturated Suction Temperature Alarm

An alarm for low suction temperature in Circuit B has been triggered. The circuit will stop to protect the compressor.

A126

A126 - Circuit A High Head Pressure Alarm

An alarm indicating high head pressure in Circuit A. The circuit will stop to prevent damage.

A127

A127 - Circuit B High Head Pressure Alarm

An alarm indicating high head pressure in Circuit B. The circuit will stop to prevent damage.

A128

A128 - Digital Scroll High Discharge Temperature Alarm

This alarm indicates high discharge temperature for the digital scroll compressor. Compressor A1 is locked off.

A140

A140 - Reverse Rotation Detected

The system has detected that a fan or compressor is rotating in the wrong direction. The unit will shut down.

A150

A150 - Unit is in Emergency Stop

The unit has received an external command to stop immediately. It will not operate until the command is cleared.

A151

A151 - Illegal Configuration - More Than Two Elec. Heat Stages

The system is configured with more than two electric heat stages, which is not allowed. The unit will shut down.

A154

A154 - Serial EEPROM Hardware Failure

There is a hardware failure with the serial EEPROM, which stores configuration data. The unit will shut down.

A156

A156 - Critical Serial EEPROM Storage Failure Error

A critical failure occurred during data storage in the serial EEPROM. This requires immediate attention as it affects essential functions.

A157

A157 - A/D Hardware Failure

There is a hardware failure in the Analog-to-Digital converter. The unit will shut down.

A168

A168 - Low Ambient Control Board (SCB2) Comm Failure

Communication has failed between the main control and the Low Ambient Control Board (SCB2). Cooling function is disabled.

A169

A169 - Expansion Valve Control Board Comm Failure

Communication has failed with the Expansion Valve Control Board. The Humidi-MiZer control is disabled.

A171

A171 - Staged Gas Control Board Comm Failure

Communication has failed with the Staged Gas Control Board. The system will stop gas heating.

A172

A172 - Staged Gas Control Board 2 (SCB2) Comm Failure

Communication has failed with the second Staged Gas Control Board (SCB2). The cooling function will be stopped.

A173

A173 - ECB1 Board Communication Failure

Communication has failed with the Economizer Control Board 1 (ECB1). The economizer and power exhaust will be stopped.

A174

A174 - ECB2 Board Communication Failure

Communication has failed with the Economizer Control Board 2 (ECB2). The entire unit will shut down.

P051

P051 - Compressor 1 Failure

This indicates a failure with Compressor 1 in Circuit A. The system will attempt to restart the compressor up to 3 times automatically.

P052

P052 - Compressor 2 Failure

This indicates a failure with Compressor 2 in Circuit A. The system will attempt to restart the compressor up to 3 times automatically.

P055

P055 - Compressor 1 Failure (Circuit B)

This indicates a failure with Compressor 1 in Circuit B. The system will attempt to restart the compressor up to 3 times automatically.

P056

P056 - Compressor 2 Failure (Circuit B)

This indicates a failure with Compressor 2 in Circuit B. The system will attempt to restart the compressor up to 3 times automatically.

P120

P120 - Circuit A Low Saturated Suction Temp - Comp A2 Shutdown

Compressor A2 in Circuit A has shut down due to low saturated suction temperature. This is a protective shutdown.

P121

P121 - Circuit B Low Saturated Suction Temp - Comp B2 Shutdown

Compressor B2 in Circuit B has shut down due to low saturated suction temperature. This is a protective shutdown.

P126

P126 - Circuit A High Head Pressure, Comp Shutdown

The head pressure in Circuit A is too high, causing the compressor to shut down or stage down. This is a protective measure.

P127

P127 - Circuit B High Head Pressure Comp Shutdown

The head pressure in Circuit B is too high, causing the compressor to shut down or stage down. This is a protective measure.

T051

T051 - Compressor 1 Failure (Locked Off)

This alert means Compressor 1 in Circuit A has failed after exceeding the automatic restart limit. The compressor is now locked off.

T052

T052 - Compressor 2 Failure (Locked Off)

This alert means Compressor 2 in Circuit A has failed after exceeding the automatic restart limit. The compressor is now locked off.

T055

T055 - Compressor 1 Failure (Locked Off, Circuit B)

This alert means Compressor 1 in Circuit B has failed after exceeding the automatic restart limit. The compressor is now locked off.

T056

T056 - Compressor 2 Failure (Locked Off, Circuit B)

This alert means Compressor 2 in Circuit B has failed after exceeding the automatic restart limit. The compressor is now locked off.

T064

T064 - Circuit A Saturated Temperature Transducer Failure

The temperature sensor for Circuit A has failed. The system will stop Circuit A to prevent damage or inaccurate readings.

T065

T065 - Circuit B Saturated Temperature Transducer Failure

The temperature sensor for Circuit B has failed. The system will stop Circuit B to prevent damage or inaccurate readings.

T072

T072 - Evaporator Discharge Reset Sensor Failure

The sensor that monitors the evaporator discharge has failed. The unit will shut down completely.

T073

T073 - Outside Air Temperature Thermistor Failure

The sensor measuring the outside air temperature has failed. The economizer function will be disabled, but the unit may continue to operate.

T074

T074 - Space Temperature Thermistor Failure

The sensor measuring the indoor space temperature has failed. The unit will shut down to prevent incorrect operation.

T075

T075 - Return Air Thermistor Failure

The sensor measuring the return air temperature has failed. The unit will continue to run, but may not control temperature accurately.

T076

T076 - Outside Air Relative Humidity Sensor Failure

The sensor measuring the outside air humidity has failed. The system will switch to using only the outside air temperature for control.

T077

T077 - Space Relative Humidity Sensor Failure

The sensor measuring the indoor space humidity has failed. The system will use a default control method based on dry bulb temperature.

T078

T078 - Return Air Relative Humidity Sensor Failure

The sensor measuring the return air humidity has failed. The system will use a default control method based on differential dry bulb temperature.

T082

T082 - Space Temperature Offset Sensor Failure

The sensor used for space temperature offset has failed. The system will operate using the space temperature without the offset.

T090

T090 - Circuit A Discharge Pressure Transducer Failure

The sensor measuring the discharge pressure for Circuit A has failed. The system will stop Circuit A.

T091

T091 - Circuit B Discharge Pressure Transducer Failure

The sensor measuring the discharge pressure for Circuit B has failed. The system will stop Circuit B.

T092

T092 - Circuit A Suction Pressure Transducer Failure

The sensor measuring the suction pressure for Circuit A has failed. The system will stop Circuit A.

T093

T093 - Circuit B Suction Pressure Transducer Failure

The sensor measuring the suction pressure for Circuit B has failed. The system will stop Circuit B.

T110

T110 - Circuit A Loss of Charge

The system has detected a loss of refrigerant charge in Circuit A. The circuit will stop to prevent damage to the compressor.

T111

T111 - Circuit B Loss of Charge

The system has detected a loss of refrigerant charge in Circuit B. The circuit will stop to prevent damage to the compressor.

T120

T120 - Circuit A Low Saturated Suction Temperature Alert

An alert indicating low suction temperature in Circuit A. The circuit will stop as a precaution.

T121

T121 - Circuit B Low Saturated Suction Temperature Alert

An alert indicating low suction temperature in Circuit B. The circuit will stop as a precaution.

T122

T122 - Circuit A High Saturated Suction Temperature

The saturated suction temperature in Circuit A is too high, potentially during startup. The circuit will stop.

T123

T123 - Circuit B High Saturated Suction Temperature

The saturated suction temperature in Circuit B is too high, potentially during startup. The circuit will stop.

T126

T126 - Circuit A High Head Pressure Alert

An alert indicating high head pressure in Circuit A. The circuit will stop.

T127

T127 - Circuit B High Head Pressure Alert

An alert indicating high head pressure in Circuit B. The circuit will stop.

T128

T128 - Digital Scroll High Discharge Temperature Alert

The discharge temperature of the digital scroll compressor is too high. Compressor A1 will be shut down to 50% capacity.

T153

T153 - Real Time Clock Hardware Failure

The internal real-time clock hardware has failed. The unit will shut down. This may affect scheduling and timing functions.

T155

T155 - Serial EEPROM Storage Failure Error

An error occurred while storing data in the serial EEPROM. This may affect unit operation and configuration.

T177

T177 - 4-20 mA Demand Limit Failure

The input for the 4-20 mA demand limit has failed. Demand limiting functions will be stopped.

T178

T178 - 4-20 mA Static Pressure Reset/VFD Fail

The 4-20 mA input for static pressure reset or VFD control has failed. These functions will be stopped.