Carrier · 38AP Air Handler
The voltage supplied to the control module (on T2-T1 terminals) is below 18 VAC for more than 5 seconds. This will stop the compressor. The system will attempt to reset after 5 minutes if the voltage is between 18 and 30 VAC. This alert does not cause a lockout.
Click steps to track your progress.
Verify that the correct 24 VAC module is installed.
Check the control circuit wiring for errors.
Ensure the T2-T1 voltage is within the acceptable range (18-30 VAC).
Allow 5 minutes for automatic reset if voltage is corrected.