Carrier 30XA/XAS/XB/XBP/XW Chillers

60 fault codes documented

10078

10078 — High discharge gas temperature, circuit A

The discharge gas temperature on circuit A is too high. Circuit A will shut down.

10079

10079 — High discharge gas temperature, circuit B

The discharge gas temperature on circuit B is too high. Circuit B will shut down.

10080

10080 — High discharge gas temperature, circuit C

The discharge gas temperature on circuit C is too high. Circuit C will shut down.

10081

10081 — Suction valve closed, circuit A

The suction valve on circuit A is closed, preventing normal operation. Circuit A will shut down.

10082

10082 — Suction valve closed, circuit B

The suction valve on circuit B is closed. Circuit B will shut down.

10083

10083 — Suction valve closed, circuit C

The suction valve on circuit C is closed. Circuit C will shut down.

10087

10087 — Slide valve control unverifiable, circuit A

The system cannot verify the slide valve control on circuit A. No action is taken by the unit, but this indicates a potential problem.

10088

10088 — Slide valve control unverifiable, circuit B

The slide valve control on circuit B cannot be verified. This may indicate an issue with solenoid valves or the current transformer.

10089

10089 — Slide valve control unverifiable, circuit C

The slide valve control for circuit C is unverifiable. This alert requires attention.

10090

10090 — Flow controller configuration fault

There is an error in the flow controller's configuration. The unit will not be allowed to restart until corrected.

10091

10091 — Flow controller fault – evaporator flow switch failure

The evaporator flow switch within the flow controller has failed. Compressors and the evaporator pump will stop.

10094

10094 — Free cooling operation failure, circuit A

Free cooling operation on circuit A has failed. Circuit A will shut down, but free cooling can restart after 30 minutes. This may be due to a refrigerant pump fault.

10095

10095 — Free cooling operation failure, circuit B

Free cooling operation on circuit B has failed. Circuit B will shut down, but free cooling can restart after 30 minutes. This may be due to a refrigerant pump fault.

10097

10097 — Water exchanger temperature sensors swapped

The temperature sensors for the water exchanger have been swapped. The unit will shut down.

10100

10100 — Electrical box fan failure (units with HFO only)

The fan in the electrical box has malfunctioned (for units using HFO). The unit will shut down.

12001

12001 — Discharge transducer fault, circuit A

The pressure transducer measuring discharge gas pressure on circuit A has a fault. Circuit A will shut down.

12002

12002 — Discharge transducer fault, circuit B

The pressure transducer measuring discharge gas pressure on circuit B has a fault. Circuit B will shut down.

12003

12003 — Discharge transducer fault, circuit C

The pressure transducer measuring discharge gas pressure on circuit C has a fault. Circuit C will shut down.

12004

12004 — Suction transducer fault, circuit A

The pressure transducer measuring suction gas pressure on circuit A has a fault. Circuit A will shut down.

12005

12005 — Suction transducer fault, circuit B

The pressure transducer measuring suction gas pressure on circuit B has a fault. Circuit B will shut down.

12006

12006 — Suction transducer fault, circuit C

The pressure transducer measuring suction gas pressure on circuit C has a fault. Circuit C will shut down.

12007

12007 — Heat reclaim pump-down pressure transducer fault, circuit A

The pressure transducer for heat reclaim pump-down on circuit A has a fault. The reclaim session will stop, and the unit will return to air-cooled mode.

12008

12008 — Heat reclaim pump-down pressure transducer fault, circuit B

The pressure transducer for heat reclaim pump-down on circuit B has a fault. The reclaim session will stop, and the unit will return to air-cooled mode.

12010

12010 — Oil pressure transducer fault, circuit A

The oil pressure transducer on circuit A has a fault. Circuit A will shut down.

12011

12011 — Oil pressure transducer fault, circuit B

The oil pressure transducer on circuit B has a fault. Circuit B will shut down.

12012

12012 — Oil pressure transducer fault, circuit C

The oil pressure transducer on circuit C has a fault. Circuit C will shut down.

12013

12013 — Economizer pressure transducer fault, circuit A

The economizer pressure transducer on circuit A has a fault. Circuit A will shut down.

12014

12014 — Economizer pressure transducer fault, circuit B

The economizer pressure transducer on circuit B has a fault. Circuit B will shut down.

12015

12015 — Economizer pressure transducer fault, circuit C

The economizer pressure transducer on circuit C has a fault. Circuit C will shut down.

15001

15001 — Evaporator entering water thermistor fault

The sensor measuring the evaporator's incoming water temperature has detected an issue. This can cause the unit to shut down.

15002

15002 — Evaporator leaving water thermistor fault

The sensor measuring the evaporator's outgoing water temperature has detected an issue. The unit will shut down.

15003

15003 — Defrost thermistor fault, circuit A

The sensor monitoring the temperature for defrost on circuit A has failed. The unit may display an alert or shut down.

15004

15004 — Defrost thermistor fault, circuit B

The sensor monitoring the temperature for defrost on circuit B has failed. In cooling mode, an alert is displayed; in heating mode, circuit B shuts down.

15006

15006 — Condenser entering water thermistor fault

The sensor for the condenser's incoming water temperature has a fault. The unit shuts down in heating mode.

15007

15007 — Condenser leaving water thermistor fault

The sensor for the condenser's outgoing water temperature has a fault. The unit will shut down.

15008

15008 — Reclaim condenser entering thermistor fault, circuit A

The sensor for the entering temperature of the reclaim condenser on circuit A is faulty. The unit will return to air-cooled mode.

15009

15009 — Reclaim condenser leaving thermistor fault, circuit B

The sensor for the leaving temperature of the reclaim condenser on circuit B has a fault. The unit will return to air-cooled mode.

15010

15010 — OAT thermistor fault

The Outdoor Air Temperature (OAT) thermistor has a fault. The unit will shut down.

15011

15011 — Master/slave common water thermistor fault

A thermistor that monitors common water temperature in a master/slave setup has failed. Master/slave operation will be disabled, and the unit will operate in stand-alone mode.

15012

15012 — Suction gas thermistor fault, circuit A

The sensor for suction gas temperature on circuit A has a fault. Circuit A will shut down.

15013

15013 — Suction gas thermistor fault, circuit B

The sensor for suction gas temperature on circuit B has a fault. Circuit B will shut down.

15014

15014 — Suction gas thermistor fault, circuit C

The sensor for suction gas temperature on circuit C has a fault. Circuit C will shut down.

15015

15015 — Discharge gas thermistor fault, circuit A

The sensor for discharge gas temperature on circuit A has a fault. Circuit A will shut down.

15016

15016 — Discharge gas thermistor fault, circuit B

The sensor for discharge gas temperature on circuit B has a fault. Circuit B will shut down.

15017

15017 — Discharge gas thermistor fault, circuit C

The sensor for discharge gas temperature on circuit C has a fault. Circuit C will shut down.

15018

15018 — Condenser subcooling liquid thermistor fault, circuit A

The sensor for condenser subcooling liquid temperature on circuit A has a fault. The unit will return to air-cooled mode.

15019

15019 — Condenser subcooling liquid thermistor fault, circuit B

The sensor for condenser subcooling liquid temperature on circuit B has a fault. The unit will return to air-cooled mode.

15021

15021 — Space temperature thermistor fault

The thermistor monitoring the space temperature has a fault. No specific action is taken, but system performance might be affected.

15023

15023 — Evaporator heater feedback thermistor fault

The feedback thermistor for the evaporator heater has a fault. No specific action is taken, but the heater function might be impacted.

15024

15024 — Economizer gas thermistor fault, circuit A

The economizer gas thermistor for circuit A has a fault. The economizer function will be disabled.

15025

15025 — Economizer gas thermistor fault, circuit B

The economizer gas thermistor for circuit B has a fault. The economizer function will be disabled.

15026

15026 — Economizer gas thermistor fault, circuit C

The economizer gas thermistor for circuit C has a fault. The economizer function will be disabled.

15030

15030 — Free cooling liquid thermistor fault, circuit A

The free cooling liquid thermistor for circuit A has a fault. The free cooling function will be disabled.

15031

15031 — Free cooling liquid thermistor fault, circuit B

The free cooling liquid thermistor for circuit B has a fault. The free cooling function will be disabled.

15032

15032 — MASTER/Slave Common Heat Fluid Thermistor Fault

The thermistor monitoring the common heat fluid in a master/slave configuration has a fault. Master/slave operation will be disabled.

15036

15036 — Dry Cooler Leaving thermistor failure

The thermistor measuring the leaving temperature of the dry cooler has failed. There is no specific action taken, but the system may not operate optimally.

15046

15046 — Free Cooling Water Loop Thermistor Failure

The thermistor monitoring the free cooling water loop has failed. Free cooling will be disabled.

15047

15047 — Free Cooling Leaving Water Thermistor Failure

The thermistor measuring the leaving water temperature for free cooling has failed. Free cooling will be disabled.

15048

15048 — Free Cooling OAT Thermistor Failure

The Outdoor Air Temperature (OAT) thermistor used for free cooling has failed. Free cooling will be disabled.

15050

15050 — Cooler Leaving Fluid #2 Thermistor Fault

There is a problem with the sensor that measures the temperature of the fluid leaving the cooler. The unit will shut down.