This alarm occurs when there is no communication between the installer module and the pool board for 90 seconds, indicating a connection or cable issue.
Click steps to track your progress.
Check and ensure secure CANbus connections on both the installer module and the pool module.
Inspect the CANbus cable for any breaks or damage; replace if necessary.
Verify that the correct type of CANbus cable is used as specified in the installer guide.
Separate the CANbus and power cables by at least 100 mm to prevent interference.