Bosch · Alarm List A/W Split (8754) 2018 01 10
This alarm is activated if the temperature JR1 is more than 5°C above TC3, and the subcooling exceeds the set point for over 5 minutes during hot water production. It indicates the heat pump is overfilled with refrigerant.
Click steps to track your progress.
Evacuate the heat pump to remove excess refrigerant.
Refill the heat pump with the exact quantity of refrigerant specified on the type plate.
Ensure the refrigerant charge is accurate to prevent recurrence.