The system is configured to use an external room temperature sensor for heating circuit 1, but communication with the module has not been established. This may be due to an incorrect software setting.
Click steps to track your progress.
Access the Service menu.
Navigate to Set heating/cooling > Heating circ. 1.
Ensure 'Ext. room temp. sensor' is set to 'No'.
Verify 'Programming unit' is set to 'RC100/CR10'.
Consult the room sensors' installer guide for further information.
Contact a qualified technician if the issue persists.